Download AutoCAD Shop Drawings for A Fire Fighting Project DWG. final working drawings for a firefighting project.
Download Also: Firefighting Project Shop Drawings
Download Also: Firefighting Project Shop Drawings
AutoCAD Shop Drawings for A Fire Fighting |
- This Drawing Shall Be Read In Conjunction With The Other Mechanical Services Drawings, Electrical Architectural.
- All Dimensions Are In Millimeter Unless Otherwise Noted.
- Fire Fighting Pipes Shall Be Black Steel Sch 40 As Pes Astm A53, Under Ground Pipes Shall Be Cpvc Sch 80 With Thrust Blocks As Per Nfpa.
- Hydrotest All Fire Water Piping System To 150% Of The Working Pressure.
- Sprinkler Locations Given, Are Subject To Changes Exact Location And Of Sprinkler To Be Determined During Shop Drawing & Final Reflected Ceiling And In Coordination With Other Provisions (Ductwork, Light Fixtures... Etc)
- The Installation And Testing Procedure Of The Fire Fighting Systems In This Drawing Shall Be In Accordance With Nfpa Latest Edition.
- The Piping Network Shall Be Installed So That The System May Be Drained.
- All Pipes Pass Thru Wall Or Slab Shall Be Thru Pipe Sleeves.
- All Exposed Pipes Shall Be Properly Insulated According To Specified Insulating Material.
- All Pipe Sizes Are In Millimeter And Are For Internal Diameter Of Pipe.
- The Pumps Motor Size To Be Verified And Adjusted If Necessary By Contractor Upon Final Selection Of Equipment, And Completion Of Shop Drawings.
- Provide Expansion Loop/ Connection Where Necessary.
- All Fire Fighting Pipes Shall Be Grounded Fire Hose Cabinet Drop Lines Location Shall Be Coordinated With Other Services At Site.
- The Pipelines Should Be Supported In Proper Intervals To Avoid Stresses In The Pipelines.
- All Embedded Pipelines Must Pass The Required Test Before Closing The Trench Or Wall.
- All Fire Fighting Pipes Shall Be Paint With Two Layer Of Epoxy And One Layer Of Fire Fighting Pipes Red Color
- All Supports And Hangers To Be In Accordance With Nfpa 13.
- Sprinklers In Public And Common Areas With Finished Ceilings
- Rooms Shall Be Fully Recessed, Concealed Type With Factory Finished Cover Plates As Directed By Architect.